The nature and quality of the
fire alarm installation work
needs to be such as to maintain the integrity of the fire alarm system and minimize the duration and extent of disablement of the system during maintenance o
r modifications. Installation practices and workmanship need to conform to the requirements of BS 7671.
Penetration of construction (e.g.
for the passage of cables, conduit,
trunking or tray)
need to be “fire stopped” to avoid the free passage of fire or smoke, regardless of whether the construction has a recognized degree of fire resistance.
Recommendations:
The following recommendations are applicable.
1) The entire electrical fire alarm system installation should conform to the requirements of BS 7671. In general, the recommendations of this standard supplement, but do not conflict with, these requirements. Where any such conflict is considered to exist, the recommendations of this standard should take precedence.
2) Cables which are directly fixed to surfaces should be neatly run and securely fixed at suitable intervals, in accordance with the recommendations of the cable manufacturer. Cables should not rely on suspended ceilings for their support.
3) The installer should ensure that all wiring complies with, at least, 26.2f) to 26.2o).
d) Joints in fire alarm cables, other than those contained within the enclosures of equipment, should be avoided
wherever practicable [see 26.2g)].
4) So far as is reasonably practicable, cable routes should be selected to follow the recommendations
.
Care should be taken to ensure the electrical continuity of electromagnetic screens, including metallic
sheaths of cables.
5) Where new conduit,
trunking or tray is installed, its capacity should be in accordance with the
recommendations given in BS 7671.
6) Where a cable passes through an external wall, it should be contained in a smooth-bore sleeve of metal
or other non-hygroscopic material sealed into the wall. This sleeve should slope downwards towards the outside and should be plugged with a suitable non-hardening waterproof compound to prevent the entry of rain, dust or vermin.
7) Where a fire alarm cable passes through an internal wall, a small clearance hole should be provided. If additional mechanical protection is necessary, a smooth-bore sleeve should be sealed into the wall.
8) Care should be taken to ensure that the ends of any sleeves are free from sharp edges which might
damage cables during installation.
9) When a cable passes through a floor, the considerations a
sleeve should extend as far above floor level as is required for protection of the cable it is to carry, but never less than 300 mm.
10) Where cables, conduits,
trunking or tray pass through floors, walls, partitions or ceilings, the surrounding hole should be as small as reasonably practicable and made good with fire stopping
materials that ensure that the fire resistance of the construction is not materially reduced. Spaces through which fire or smoke could spread should not be left around the cable, conduit,
trunking or tray.
11) If cables or conduits are installed in channels, ducts,
trunking or shafts that pass through floors, walls, partitions or ceilings, barriers with the appropriate level of fire resistance should be provided
within the channels, etc.
to prevent the spread of fire unless, in the case of
ducts and shafts, the construction of the duct or shaft affords equivalent fire resistance to the structure penetrated; in the
latter case
fire stopping need only be provided where cables pass into, or out of, the duct or shaft.